Motor
Brushless EC motor with high efficiency and low consumption, supply 230V +/- 10%-50/60Hz, IP44, ball bearings, thermal protection and ON/OFF switch.
Additional information
Working temperature between -20ºC up to +40ºC. This cabinet fan is suitable for mounting in any orientation and designed for indoor use.
Integrated control
It is supplied with integrated plug&play control, pre-configured to work at constant pressure (COP) with the following pressure setpoint depending on the model:
– CAB-125: 100 Pa
– CAB-150 a 315: 150 Pa
– CAB-355 and 400: 200 Pa
By acquiring the programmation console PROSYS ECOWATT, there will be access to the settings of constant pressure mode (COP) in addition to other 3 modes:
– Constant airflow (CAV)
– Proportional (VAV)
– Minimum-Maximum
– Timer (in combination with TIMER RTC accessory).
Constant pressure mode (COP)
– Minimum speed of fan between 0-50%
– Maximum speed of fan between 50-100%
-Night position adjustable between 25-100% of pressure at maximum speed.
Constant airflow mode (CAV)
(except 125 model)
– Minimum speed of fan between 0-50%
– Maximum speed of fan between 50-100%
– Night position adjustable between 25-100% of airflow at maximum speed.
Proportional mode (VAV)
– Up to 2 analogue inputs, 0-10V or 4-20mA.
– Maximum demand selection when 2 analogue inputs are connected
– Minimum speed of fan between 0-50%
– Maximum speed of fan between 50-100%
– Alarm relay output
Minimum-maximum mode
– Digital input to select speed
– Minimum speed of fan between 0-50%
– Maximum speed of fan between 50-100%
Timer (RTC)
By acquiring TIMER RTC accessory jointly with programmation console PROSYS ECOWATT the unit can be set to work in time bands.
– Until three daily periods with the desired instruction.
– Holiday period.
Modbus RTU
This series is able to be controlled and displayed via Modbus-RTU network.
-
ON-OFF switch
-
Low noise level
Acoustic insulation of 50 mm thickness fireproof fibreglass (M0) with a high resistance coating reducing the noise level significantly. -
Sound-absorbent insulation at the inlet.
-
Direct drive backward centrifugal impeller
-
Installation in any orientation
Possibility to be installed upright, horizontal or inverted.